According to French standards, how many electrical outlets can be connected to the same circuit (or circuit breaker)?
Merged questions
Answer
Submitted by Answiki
on 06/22/2022 at 07:23:45 PM UTC
The NF C 15-100 standard specifies that the maximum number of outlets per circuit is :
- 8 outlets for a 1.5 mm² cable circuit with a 16 A circuit breaker.
- 12 outlets for a 2.5 mm² cable circuit with a circuit breaker up to 20 A.
Note that classically,
- the light circuits are wired in 1.5 mm² on a 10 A circuit breaker
- socket circuits are wired in 2.5 mm² on a 16 A circuit breaker
- the specialized socket circuits are wired in 2.5 mm² on a 20 A circuit breaker
See also :
- According to French standards, how many lighting points can be connected to a circuit breaker?
- In the French NF C 15-100 standard, what is a light point?
Question by Answiki 06/22/2022 at 07:23:53 PM
According to French standards, how many electrical outlets can be connected to the same circuit (or circuit breaker)?
Answer by Answiki on 06/22/2022 at 07:23:45 PM
The NF C 15-100 standard specifies that the maximum number of outlets per circuit is :
- 8 outlets for a 1.5 mm² cable circuit with a 16 A circuit breaker.
- 12 outlets for a 2.5 mm² cable circuit with a circuit breaker up to 20 A.
Note that classically,
- the light circuits are wired in 1.5 mm² on a 10 A circuit breaker
- socket circuits are wired in 2.5 mm² on a 16 A circuit breaker
- the specialized socket circuits are wired in 2.5 mm² on a 20 A circuit breaker
See also :
- According to French standards, how many lighting points can be connected to a circuit breaker?
- In the French NF C 15-100 standard, what is a light point?
Question by Answiki 06/22/2022 at 07:21:53 PM
According to French standard, how many electrical outlets can be connected to the same circuit (or circuit breaker)?
# | ID | Query | URL | Count |
---|
Icons proudly provided by Friconix.